Power Line Communication in Medium Voltage Systems: Characterization of MV Cables
2008
The aim of this paper is to illustrate the development of a theoretical and experimental study on the characterization of medium voltage (MV) cables in the frequency range 25-200 kHz. Two transmission line configurations, line-ground and line-line, were considered in order to evaluate the main parameters, such as the characteristic impedance and the attenuation constant alpha. A simplified model of the line-ground configuration is proposed which allows one to evaluate the characteristic impedance and the attenuation constant by means of geometrical dimensions. The model was verified by experimental measurements on commonly used MV cables, RG7H1R, with an aluminium core of different sections…
Model of line to shield power line communication system on a Medium Voltage network
2010
In this paper a complete model of a power line communication (PLC) system on a Medium Voltage (MV) network is presented in the case of a line-ground configuration. A simple and friendly Simulink (R) software is used to develop the model. A distributed parameter MV cable model in line-ground configuration is considered together with the power transformers, the signal coupling networks and the receiving and transmitting line coupling interface of a ST7540 FSK powerline transceiver. The performances of the complete PLC communication system are evaluated for different line lengths by means of the attenuation computed as ratio between the received and transmitted voltage signals.